Viessmann Vitotronic 300 Installation And Service Instructions Manual page 45

Type gw5b, vitotronic 300, type gw5b weather-compensated, digital boiler control unit for boiler model cm2 - 400, 500, 620 and 620 tx
Table of Contents

Advertisement

Vitotronic 300, GW5B Installation and Service
Fault Codes
(continued)
Displayed
System characteristics
fault code
C2
Control mode
C8
Boiler cools down
C9
Boiler cools down
CA
Boiler cools down
CB
Boiler cools down
CD
Control mode
CE
Control mode
CF
Control mode
No communication
via LON.
D1
Boiler cools down
D2
Control mode
D3
Control mode
D4
Boiler cools down
D6
Control mode
Cause
Lead break, KM BUS to solar
control module or Vitosolic.
Fault, low water indicator at
"X7" of plug-in adaptor 1 for
external safety equipment
Fault, maximum pressure limiter
at "X3" of plug-in adaptor 1 for
external safety equipment
Fault, minimum or maximum
pressure limiter 2 at "X2" of
plug-in adaptor 1 for external
safety equipment.
Additional high limit safety
cut-out fault
Communication fault, Vitocom
100, type GSM2.
Communication fault, plug-in
adaptor 1 for external safety
equipment.
Communication fault, control unit
LON communication module.
Burner fault
Communication fault, plug-in
adaptor 2 for external safety
equipment.
Communication fault, extension
EA1.
The fuse F2 has blown.
Input DE1 at extension EA1
reports a fault.
Troubleshooting
Measures
Check KM BUS cable and
appliance.
Without solar control unit:
Set code "54:0" in the "General"
group.
Check the water level of
the system; reset low water
indicator.
Check the system pressure and
reset the maximum pressure
limiter.
Check system pressure and reset
minimum or maximum pressure
limiter 2.
Check the system temperature
and reset the high limit safety
cut-out.
Check connections and Vitocom
100 (see separate installation
and service instructions).
Without Vitocom 100: Set code
"95:0" in the "General" group.
Check plug-in adaptor (see page
129). Without plug-in adaptor:
Set code "30:0" in the "General"
group.
Check LON communication
module and replace if required.
If no LON communication module
is installed, set code "76:0" in
the "General" group.
Check the burner.
Check plug-in adaptor (see page
131). Without plug-in adaptor:
Set code "31:0" in the "General"
group.
Check connections (see page
137). Without extension EA1:
Set code "5B:0" in the "General"
group.
Check fuse F2.
Remove fault at appliance
concerned.
45