Kozy Heat #816-Cl Co-Linear Vent System - kozy heat Chaska CSK-31 Installation Manual

Direct vent fireplace insert
Table of Contents

Advertisement

KOZY HEAT #816-CL CO-LINEAR VENT SYSTEM

The co-linear pipes included in this vent system are designed to extend up to 35ft. (10.67m)
IDENTIFICATION: Exhaust Pipe: red marking.
IMPORTANT
Proper operation of this insert requires exhaust and combustion air pipes be connected to correct collars on termination kit and
insert air duct.
A. Carefully extend exhaust and combustion air intake pipes to equal total chimney length required.
If using stub method for combustion air pipe, extending it is not necessary. Determine length needed from air duct on insert (4ft.
NOTE
(1.22m) minimum) to above damper opening in existing chimney. Remove excess combustion air pipe from end without a collar.
Continue with Step B. #2 below.
Full Connection Method: Slide intake pipe (end without collar) over termination cap collar. Secure with 3 self-tapping screws (provided).
B.
Place bead of sealant around inner edge at end of exhaust pipe (without collar / red marking) and slide onto corresponding collar on
termination cap (collar with label). Secure with 3 self-tapping screws (provided). Apply additional sealant around joint to ensure a
proper seal.
EXHAUST COLLAR ON FIREPLACE AIR DUCT IS ON RIGHT SIDE. INSTALL TERMINATION CAP WITH EXHAUST COLLAR ON
IMPORTANT
RIGHT SIDE.
EXHAUST COLLAR
(Extends through middle divider plate)
TERMINATION CAP
INTAKE COLLAR
(Extends through bottom plate)
SHEET METAL SCREWS (3 TOTAL)
Your vent cap may look slightly different than one shown.
Figure 9a
SEALANT
9
SEALANT