S .I .T. PRO FL A ME 2 I FC I G NI T I O N AND RE S E T I NFO RMAT I O N
IGNITION SEQUENCE
Starting from OFF, press remote control ON button. Approximately (4) seconds after ON/OFF button is pushed, the IFC control module
will start the spark. First ignition try will last approximately (60) seconds.
If there is no flame ignition (rectification) during the first try for ignition, the IFC control module will stop sparking for approximately (35)
seconds. After this wait time, the IFC control module will start the second try for ignition by sparking for approximately (60) seconds.
If ignition is successful on third ignition attempt, there will be a (60) second delay before the main burner lights.
If after this third attempt there is still no positive ignition, the IFC control module will go into LOCK OUT and the red LED will blink (3)
times in intervals until the system is reset.
LED Indicator Location
: Corner of IFC control module. (IFC control module location determined by fireplace model and design. May
LOCK OUT = LED blinks (3) times in intervals until the system is reset.
In Summary:
1.
The IFC control module will try (2) times for ignition.
2.
Each try for ignition will last approximately (60) seconds.
3.
The wait time between the two tries is approximately (35) seconds.
RESET IFC CONTROL MODULE WHEN SYSTEM GOES INTO LOCK OUT
Reset Using ON/OFF Switch:
Set ON/OFF switch to OFF position. Wait approximately (2) seconds and move switch to the ON position. The ignition sequence will start
again.
Reset Using Remote Control ON/OFF Button:
Turn the system off by pressing the remote control ON/OFF button. After approximately (2) seconds press the remote control ON/OFF
button again. The IFC control module will reset and the ignition sequence will start again.
:
Reset By Cycling Flame
In the Manual Flame Control Mode, use the Down Arrow Button to reduce flame to off (indicated by OFF displayed on Remote Control
Display Screen). Wait approximately (2) seconds and press the Up Arrow Button, the ignition sequence will start.
A D D I T I O N A L D I A G N O S T I C I N D I C A T I O N S I N F O R M A T I O N
Low Battery Condition (<4V) Remote Control: Battery Icon will appear on LCD remote control display. Replace batteries.
Low Battery Condition (<4V) Battery Backup: Red LED Indicator will blink (1) time in intervals. Low double-beep emitted from IFC
control module when it receives an ON/OFF command from the remote control. Replace Batteries.
Pilot Flame Error Condition: Red LED Indicator will blink (2) times in intervals. Contact your dealer if this occurs.
System Lock Out Condition: Red LED Indicator will blink (3) times in intervals. Make sure gas is turned on. Make sure sensor is not
shorted. Follow Reset IFC Control Module When System Goes Into Lock Out instructions above.
Up & Down
Arrow Buttons
Figure 9a
SYSTEM OPERATION
be located in component housing behind lower grill, or behind left side access panel).
Remote Control
ON/OFF Button
LEDs
9
IFC Control Module