Conversion to Co-Linear Liners using generic Co-Linear Adapters
Co-linear portion of vent system may only be installed
within a solid-fuel burning fi replace and chimney.
The appliance must not be connected to a chimney fl ue
serving a separate solid-fuel burning appliance.
Requires a Co-Axial to Co-Linear appliance Adapter,
Rules for Co-Linear Venting
• Maximum 40 feet vertical pipe
• Minimum 10 feet vertical
• Maximum offset 8 feet with liners
at minimum 45 degrees from
horizontal plane
• Restrictor: Use #4 position for all
co-linear installations—refer to
page 30 for restrictor positioning.
7-1/8"
(181 mm)
7-1/2"
(191 mm)
Dura-Vent #46DVA-GCL Co-Axial
to Co-Linear Adapter
Any fi nishes
applied
around the
fi replace
must be non-
combustible
Co-linear terminal confi gurations
10"
10"
7-5/8" dia.
collar
3" Inlet & Exhaust
Collars
559CLT Co-Linear Terminal

Co-linear Venting

Co-linear
adapter
3"
(76 mm)
10-1/2"
(267 mm)
NOTE: Appliance needs to
be framed as indicated in
previous sections. All zero
clearance stand-offs required.
Co-Linear installation into existing chimney
559FSK Flashing Kit
two lengths of 2-ply 3" dia. fl exible chimney liner
approved for venting gas appliances, a co-linear
termination kit and fl ashing or a co-linear to co-axial
adapter and either a high wind vertical vent terminal
cap or a low profi le vertical termination.
2 x 3"
liners
Flashing
3" min.
bend radius
Co-linear
adapter
Linear
engine
Alternate to 559CLT/559FSK Conversion
Terminal Cap
QUALIFIED
INSTALLER
Approved co-linear
termination or approved
co-linear adapter
and approved
co-axial
termination
2 x 3"
liners
Co-Linear to Co-Axial
Adapter
Flashing
33