7.2 Wiring inside and outside the panel

7.2.1
Wiring inside
Run power lines, servo amplifier drive wires, and communication cables so that they do not cross each other.
Noise interference that is generated by cables that cross each other may cause malfunctions.
Surge suppressors are an effective way to filter out surge noise that is generated from no fuse breakers
(NFB), electromagnetic contactors (MC), relays (RA), solenoid valves, and induction motors.
Refer to the section to follow for surge killers.
7.2.3 Attaching surge killers to control equipment
Uncrossed power lines and
communication cables
Power
cable
PLC
NFB
MC
MC
Drive control wire
Terminal block
7.2.2
Outside the panel
To pull the power line and communication cable out of the panel, make two pullout holes away from each
other and pull the cables through.
Putting both cables through the same pullout hole will increase noise interference.
Connection
cable
Keep the power line and communication cable inside the duct at least 100 mm away from each other.
If that is not possible, the use of a metal separator inside the duct can reduce noise interference.
GOT connection cable
PLC I/O wire
RA
RA
Power line
Power line
Pullout hole
Power line
100mm or more
Signal line
Crossing power lines and
communication cables
Power
cable
PLC
NFB
MC
MC
Drive control wire
Terminal block
Connection
cable
Pullout hole
Wiring duct
Separator
Power line
Signal line
7.2 Wiring inside and outside the panel
7.2.1 Wiring inside
GOT connection cable
PLC
I/O wire
RA
RA
7 - 8
1
2
3
4
5
6
7
8