Freeze-Up Protection Control; Heating Peak-Cut Control - Daikin F-Series Service Manual

Inverter multi f-series
Hide thumbs Also See for F-Series:
Table of Contents

Advertisement

SiEN12-710A
2.6

Freeze-up Protection Control

Outline
During cooling operation, the signals being sent from the indoor unit allow the operating
frequency limitation and then prevent freezing of the indoor heat exchanger. (The signal from
the indoor unit must be divided into the zones as the followings.
Detail
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 sec from
operation start and after 30 sec from changing number of operation room.
Control in Each Zone
2.7

Heating Peak-cut Control

Outline
Heat Pump Only
During heating operation, the signals being sent from the indoor unit allow the operating
frequency limitation and prevent abnormal high pressure. (The signal from the indoor unit must
be divided as follows.)
Detail
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 min from
operation start and
Control in Each Zone
The maximum value of heat exchange intermediate temperature of each indoor unit controls the
following (excluding stopped rooms).
Function and Control
13°C
Reset zone
7°C
Up zone
5°C
Keep zone
3°C
Drooping zone
0°C
Stop zone
sec from changing number of operation room.
When increase
30
When decrease
2
Heat exchanger
thermistor temperature
Heat exchanger
thermistor
temperature
Control Specification
Return from stop
(R4561)
Stop zone
Drooping zone
Keep zone
Up zone
Reset zone
49