Troubleshooting
4.3
Freeze-up Protection Control or High Pressure Control
A5
Remote Control
Display
Method of
" High pressure control (heat pump model only)
Malfunction
Detection
" The freeze-up protection control (operation halt) is activated during cooling operation
Malfunction
" High pressure control
Decision
Conditions
" Freeze-up protection
When the indoor unit heat exchanger temperature is below 0°C during cooling operation.
Supposed
" Operation halt due to clogged air filter of the indoor unit.
Causes
" Operation halt due to dust accumulation on the indoor unit heat exchanger.
" Operation halt due to short-circuit.
" Detection error due to faulty indoor unit heat exchanger thermistor.
" Detection error due to faulty indoor unit PCB.
110
During heating operations, the temperature detected by the indoor heat exchanger
thermistor is used for the high pressure control (stop, outdoor fan stop, etc.)
according to the temperature detected by the indoor unit heat exchanger thermistor.
During heating operations, the temperature detected by the indoor heat exchanger
thermistor is above 65°C
SiEN12-710A
Service Diagnosis