Removal Of The Thermistors - Daikin F-Series Service Manual

Inverter multi f-series
Hide thumbs Also See for F-Series:
Table of Contents

Advertisement

SiEN12-710A
1.6

Removal of the Thermistors

Procedure
Step
1. Remove the assembly of
thermistor
1
Undo the clip and
remove the discharge
pipe thermistor.
2
Cut off the clamp to
remove the heat
exchanger thermistor.
The outdoor air /
3
discharge pipe / heat
exchanger thermistors
are united as one
assembly.
4
The figure shows the
arrangement of the
assembly of thermistor
[S90].
2. Remove the liquid / gas
pipe thermistor
1
Remove the liquid / gas
pipe thermistor.
Removal Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Discharge pipe thermistor
Heat exchanger
thermistor
" Be careful not to lose the clip
for the discharge pipe
thermistor.
(R7630)
" The clamp is always
reserved.
" Be careful not to lose the
clips for each thermistor.
(R7631)
Outdoor air
thermistor
(R7632)
(R7633)
Outdoor Unit
Points
(R7702)
173