SiEN12-710A
4.21 Insufficient Gas
U0
Remote Control
Display
Method of
Gas shortage detection I :
Malfunction
A gas shortage is detected by checking the power consumption value and the compressor
running frequency.
Detection
Malfunction
Gas shortage detection I :
Decision
Power consumption < 4578 / 256 (W/Hz) × Compressor running frequency – 638 (W)
However, when the status of running frequency > 48 (Hz) is kept on for a certain time.
Conditions
If a gas shortage error takes place 4 times successively, the system will be shut down. The error
counter will reset itself if this or any other error does not occur during the following 60-minute
compressor running time (total time).
Supposed
" Refrigerant shortage (refrigerant leakage)
Causes
" Poor compression performance of compressor
" Stop valve closed
" Electronic expansion valve defective
Service Diagnosis
Troubleshooting
139