Four Way Valve Performance Check - Daikin F-Series Service Manual

Inverter multi f-series
Hide thumbs Also See for F-Series:
Table of Contents

Advertisement

Check

5.1.4 Four Way Valve Performance Check

Check No.05
(Fig. 1)
148
Turn off the power and turn it on
again.
Start the heating-mode run.
S80 voltage
at DC 220-240 V with
compressor on? (Fig. 1)
YES
Disconnect the four way valve coil
from the connector and check the
continuity.
Four way
valve coil resistance at
1500 ohms?
YES
Voltage at S80
DC220-240V
Compressor
ON
* Four way valve coil
Cooling / dry : No continuity
Heating : Continuity
NO
NO
Time
SiEN12-710A
Replace the outdoor unit
PCB.
Replace the four way valve
coil.
Replace the four way valve.
(R7156)
Service Diagnosis