4.16 DC Voltage / DC Current Sensor Abnormality

H8
Remote Control
Display
Method of
DC voltage or DC current sensor system fault is identified based on the compressor operation
Malfunction
frequency and the input current detected by the product of DC current and DC voltage.
Detection
Malfunction
When the compressor operation frequency is more than 52 Hz
Decision
and when the DC current is less than 0.3 A or DC voltage is less than 50V.
" If this error repeats 4 times, the system will be shut down.
Conditions
" The error counter will reset itself if this or any other error does not occur during the following
Supposed
" Power transistor defective
Causes
" Internal wiring broken or in poor contact
" Reactor defective
" Outdoor unit PCB defective
" Refrigerant shortage
Troubleshooting
Replace the outdoor unit PCB.