3. Slide the top of the control panel onto the
retainer tabs (the slots under the top of the
frame). When the control panel is in the
retainer tabs, it rests on the posts.
4. Secure the bottom of the circuit board by
inserting and tightening the screws at the two
bottom corners through the support posts and
the retainer holes Figure 4.
Connect the supplied ground wire
between the door and the enclosure using
the supplied nuts before the circuit board
is installed.
A second ground wire is provided for connecting
the AC power ground. Both grounds connect to the
stud in the enclosure to the left of the circuit board.
Refer to Figure 3 on page 16.
Figure 4:
Standoff and Support Post
Installation
1
2
1 - 1/8 in. nylon standoff
2 - Retainer holes
3 - Support post assembly
4 - Corner of circuit board
5 - Support post
6 - Retainer hole in enclosure
1.6

Installing Optional Equipment

Two expansion options connect directly to the
control panel, and are automatically detected and
supervised when the control panel is powered:
FPD-7034 Four Point Expander
D7039 Multiplex Expansion Module
When the control panel is powered after installing
one of these options, the control panel displays
one of the following windows:
4Z EXP DETECTED
PRESS ENTER KEY
MUX DETECTED
PRESS ENTER KEY
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
FPD-7024 | Operation and Installation Guide | 1.0
3
4
5
=
6
Press the [#/Enter] key to confirm the installation of
the device and automatically set it up for
supervision.
If the [#/Enter] key is not pressed during the power-
up time-out period, the control panel resumes
operation using the last confirmed status of the
affected expander and displays an installation error
condition.
Expansion devices such as point
expanders and multiplex expanders are
disabled if they are removed from the
control panel configuration after
installation. You cannot disable
supervision of these devices when they
are installed.
Refer to the installation instructions for these
expanders for additional information.
When the D7039 Multiplex Expansion
Module is first installed, the system
displays an EEPROM fault. Execute the
default procedure to synchronize the
EEPROM on the expansion module to
the EEPROM in the control panel.
Remove power to the control panel, then
reapply power and re-install option bus
devices after the default procedure.
Replacing a D7039 Multiplex Expansion
Module causes the loss of programming
of expansion points and PINs.
Reprogram all multiplex point and PINs if
you replace the D7039.
When the D7039 is first installed, or anytime the
control panel is powered with a D7039 that has no
points programmed, the system automatically
starts the multiplex auto-programming process:
AUTO PROGRAM?
:YES(1)/NO(0)
Pressing the [1] key starts auto-programming, and
pressing [0/Prog] allows the control panel to
continue normal startup. The menu automatically
closes with NO selected if no key is pressed after
several minutes. Refer to Section 5.9.4 Auto
Program on page 74 for detailed instructions on the
auto-programming mode.