Table 7:
Alarm Load Battery Size (Ah)
Alarm Load Battery Size Chart
Grand Total Standby Existing
250 to 500 mA
501 to 999 mA
1.0 to 1.5 A
1.6 to 2.0 A
2.1 to 2.5 A
2.6 to 3.0 A
3.1 to 3.5 A
3.6 to 4.0 A
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
FPD-7024 | Operation and Installation Guide | 1.0
Capacity
Capacity
Required for 5
Required for 10
Minutes
Minutes
0.1
0.1
0.1
0.2
0.2
0.3
0.2
0.4
0.3
0.5
0.3
0.6
0.4
0.7
0.4
0.8
Capacity
Capacity
Required for 15
Required for 30
Minutes
Minutes
0.2
0.3
0.3
0.6
0.5
0.9
0.6
1.2
0.8
1.5
0.9
1.8
1.1
2.1
1.2
2.4
Overview
Capacity
Required for 45
Minutes
0.5
0.9
1.4
1.8
2.3
2.7
3.2
3.6
13