Operating Instructions

Understanding the Built-in Keypad
The keypad built into the control panel is an alphanumeric LCD keypad. It
has a two-line by 16-character display that provides information on vari-
ous control panel functions. In most instances, the top line of the display
provides general system status information, while the second line describes
specific devices that might be relevant to the current system status. When
keys are pressed, the display shows the current action on the top line,
while showing rotating menu choices on the second line. A built-in sounder
is used to annunciate keystroke entries and as an interior warning device.
Modes of System Operation
The green Power LED lights when AC power is present,
and flashes when the unit is operating from battery power.
The red Alarm LED lights whenever the system has
registered an alarm and is not reset.
The yellow Supervisory LED lights whenever the system
registers a supervisory condition.
Scroll keys are used to move through the
off-normal events indicated on the display.
4
6
2
The Disable key allows the system to disable or re-enable
inputs, notification appliance circuits or relays (outputs),
and the dialer.
The Test key allows one of seven special test modes
to be selected.
While programming, the Back key can be used to exit
menus or exit programming mode entirely.
The Programming key selects the programming mode.
Normal Operation: When the system is operating normally,
er LED is lit, and no other LEDs are lit. If the system is programmed to require a PIN,
of the LCD screen. Otherwise, the control panel bypasses this display and shows the date and time.
Alarm Operation: When an alarm occurs, the top line of the display shows
system display. The second line of the display shows
affected point. The built-in sounder turns on with a steady tone and outputs programmed to activate with the current alarm con-
dition(s) activate.
Trouble Operation: When a trouble condition occurs (such as wiring for a point is cut, AC power fails, and so on), the sounder
activates briefly, every 10 sec. The Trouble LED lights and
USE ACK/FUNC
line of the display shows
Supervisory Operation: When a supervisory condition occurs the sounder activates briefly, every 10 sec. The Supervisory
SUPERVISORY(xxx)
LED lights and
FUNC
, alternating with the programmed description for the supervisory event.
Using PIN Numbers: On systems configured with no requirement for PIN numbers, commands such as Reset and Silence are
performed by pressing the appropriate key once the panel is opened to access the keys. For systems requiring a PIN number,
first enter the user's assigned four-digit PIN number. Once the list of available options appears, simply press the key for the
desired command.
T
he
is used as the Acknowledge button. When pressed, the keypad and control panel piezo will silence, but the NACs will
not be affected. Pressing
details of an off-normal condition within the group selected. Pressing
leases control of the panel. If this is not done, it will automatically time out in 3 min.
Fire Alarm Control Panel FPD-7024
8
USE ACK/FUNC
, alternating with the programmed description for the trouble event.
appears in the top line of the display. The second line of the display shows
allows stepping through the groups of off-normal conditions. Pressing
This document must be framed and mounted
in view adjacent to the FACP.
3
1
2
4
5
6
8
7
9
0
SYSTEM NORMAL
appears on the top line of the display, the Pow-
ALARM(xxx)
, alternating with the programmed description for the
TROUBLE(xxx)
appears in the top line of the display. The second
returns you to the main menu. If pressed again, it re-
The yellow Trouble LED lights whenever the system has
detected a problem with its wiring or internal circuitry
and remains lit until the underlying trouble condition is
corrected. The trouble LED flashes while programming
mode is active.
The yellow Silenced LED lights when an alarm or trouble
condition is manually silenced by the user and turns off
when the condition that was silenced is corrected.
The yellow Ground Fault LED lights whenever a ground
fault is present on the system.
The Drill key is used to activate the local notification
appliance circuits manually.
Use the Acknowledge key to silence local keypad
sounders and to view off-normal conditions.
The Silence key quiets the bells/sirens for an alarm or
trouble condition.
The Reset key briefly turns off power to detectors to
reset them and clears any off-normal conditions.
The History key allows the record of system events to
be viewed.
The Enter key is used to accept data when in
Programming mode.
ENTER PIN:
appears on the second line
. This display overrides any other
or
allows you to view
USE ACK/

Advertisement

loading

Summary of Contents for Bosch FPD-7024

  • Page 1: Operating Instructions

    Fire Alarm Control Panel FPD-7024 Operating Instructions Understanding the Built-in Keypad This document must be framed and mounted in view adjacent to the FACP. The keypad built into the control panel is an alphanumeric LCD keypad. It has a two-line by 16-character display that provides information on vari- ous control panel functions.
  • Page 2 F01U008461-03 04/16 © 2016 Bosch Security Systems, Inc. Operating Instructions FPD-7024 130 Perinton Parkway, Fairport, NY 14450-9199 USA (800) 289-0096 Page 2 of 2...