device wires on the terminals for the few seconds it takes to program. The programming operation retries up
to three times if the device does not connect right away.
POINT NUMBER 009
ATTACH DEVICE
Then, the display automatically shows:
POINT NUMBER 009
PROGRAMMING
If the device added is an I/O module, you are asked to enter the four zones to control the relay output, just as
for other relay devices:
OUTPUT ZONE A: __
(00 - 63): __
Enter the first zone (00 to 63) you want to assign to this output and press [#/Enter]. A similar display for Zone
B, C and D appears allowing up to four zones to control this output. When all four zones are assigned, the
previous window appears. It confirms the programming operation and returns to the previous menu.
POINT NUMBER 009
PROGRAMMED
If a device is defective or not connected properly, the control panel shows:
ERROR -
DEVICE FAILED
Fast Programming
Fast programming proceeds the same as normal programming, except that when the device is programmed
you are asked to remove the device:
POINT NUMBER 009
REMOVE DEVICE
Then, you are asked to attach the next device at the next address:
POINT NUMBER 010
ATTACH DEVICE
This process continues until you press [*/Back]. All devices to be programmed must be of the same type.
5.9.3

MUX Bus Type

Shortcut: 0-
This option configures the system for two independent Class B, Style 4 buses allowing addresses up to 255.
Class A operation is not supported by the D7042 Eight Input Module; do not select Class A
operation.
The following window appears:
MUX BUS TYPE (__)
CLASS A
1-
CLASS B
2-
Press [2] to select Class B operation if the setting was changed from the default setting. Refer to
D7042/D7042B Multiplex Eight Input Remote Modules Installation Instructions (P/N: 42638) for wiring details
for a Class B configuration.
Refer to the D7039 Multiplex Expansion Module's Installation Guide (P/N: 38685) for more information
regarding Class A and Class B wiring instructions.
Refer to Figure 13 on page 74 for mounting locations inside the FPD-7024's enclosure for the D7039 and its
I/O module.
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
FPD-7024 | Operation and Installation Guide | 5.0
, 9-
PROG
PROGRAM MUX 3- BUS TYPE
Control Panel Programming
73