Point Function - Bosch FPD-7024 Operation And Installation Manual

Fire alarm control panel
Hide thumbs Also See for FPD-7024:
Table of Contents

Advertisement

FPD-7024 | Operation and Installation Guide | 5.0
5.4.2

Point Function

Shortcut: 0-
There are 16 point functions, each of which has programmable features for: configuration (fire, waterflow, and
so on), local only operation, silencing, and loop response.
The following window appears:
POINT FUNC. (__)
(01 - 16): ___
Enter the function number you wish to program and press [#/Enter]. The following window appears:
PROG FUNCT
CONFIGURE
0-
LOCAL ONLY
1-
(reserved)
2-
SILENCABLE
3-
LOOP RESPONS
4-
(reserved)
5-
<DRILL> NXT FCT
<HIST> PREV FCT
Enter the function you wish to program.
Configure
Shortcut: 0-
1. Fire: When activated, the point shows FIRE ALARM on control panel and keypads, activates selected
output devices, and sends a Fire Alarm report (if programmed). Fire points are defaulted to a latch when
first configured.
2. Waterflow: When activated, the point shows WATERFLOW ALARM on control panel and keypads,
activates selected output devices, and sends a Waterflow Alarm report (if programmed). Waterflow points
are defaulted to a non-verify characteristic when first configured.
3. Supervisory: When activated, the point shows SUPERVISORY ALARM on control panel and keypads,
and sends a Supervisory Alarm report (if programmed). Supervisory points are defaulted to a non-verify
characteristic when first configured.
4. Reset: When activated, the point initiates a control panel-reset operation to clear alarms and reset smoke
detectors. Only points 1 to 8 can be configured as reset points.
5. Silence: When activated, the point initiates a control panel silence operation to turn off sounders if the
control panel is configured to allow silencing. Only points 1 to 8 can be configured as silence points.
6. AC Fault: When activating, the control panel waits for the AC Delay Timer to expire before indicating or
sending a trouble condition. When the timer expires, it shows an AC Fault on the control panel and the
trouble LED turns on.
Enter the point number you wish to program and press [#/Enter]. The display scrolls through the PROG
FUNCTION options.
Press [0/Prog] to select CONFIGURE. The following window appears:
50
, 4-
, 2-
PROG
PROG INPUTS
, 4-
, 2-
PROG
PROG INPUTS
Control Panel Programming
POINT FUNCTION
POINT FUNCTION
Bosch Security Systems, Inc. | 1/10 | F01U008458-03

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents