Outdoor Unit; Type - Sanyo SPW-X483GH56 Installation Instruction

Eco multi system air conditioner
Table of Contents

Advertisement

Outdoor Unit

AVOID:
heat sources, exhaust fans, etc.
damp, humid or uneven locations.
DO:
choose a place as cool as possible.
choose a place that is well ventilated and outside
air temperature does not exceed maximum 45 ˚C
constantly.
allow enough room around the unit for air intake /
exhaust and possible maintenance. (Fig. 2-2)
provide a solid base; about 15 cm above ground
level to reduce humidity and protect the
unit against possible water damage and
decreased service life.
use anchor bolts or equal to bolt down the
unit, reducing vibration and noise.
Multiple installation
Unit spacing if air discharge chamber is not used.
Min. 1m
If you would like to make the separation smaller on the
air-discharge side, use an air-discharge chamber.
You can install any number of units side-by -side.
provide a solid base (concrete block, 10 × 40 cm
beams or equal), a minimum of 15 cm above
ground level to reduce humidity and protect the unit
against possible water damage and decreased
service life.
use anchor bolts or equal to bolt down the unit,
reducing vibration and noise. (Fig. 2-3)

48 Type

Min.
1 cm
Unit spacing when air discharge chamber is used.
Min. 1.5m
Min. 1m
Min. 1 m
Min. 35 cm
Min. 30cm
Min. 3.5m
Min. 35 cm
Min. 20cm
Only up to 3 units can be installed side-by-side under the
above conditions. The next group must be spaced at least
30 cm away from the first group.
14
Hot air
Out-
door
unit
Fig. 2-1
Top view
Min.20 cm
Min.50 cm
0818_C_I
Fig. 2-2
Min. 20 cm
Min. 30 cm
Air in
Air
discharge
Anchor bolts
(4 pieces)
Fig. 2-3
S4179544
Exhaust fan
Heat source
0591_C_I
Side view
Obstacle above
Min.
1 cm
Min.
2 m
Air
dis-
charge
Ground
0486_C_I
Min. 1 m
Air
discharge
chamber
Min. 30 cm
0816_C_I
Air in
Min. 15cm
0425_C_I
Min.
2 m