Other Control; Operation Of Solenoid Valves; Outdoor Unit Electronic Control Valve (Motor Valve) Control [Mov1] - Sanyo Mini ECO-i CHXR03652 Service Manual

Table of Contents

Advertisement

4. Other Control 5. Operation of Solenoid Valves

6. Outdoor Unit Electronic Control Valve (Motor Valve) Control [MOV1]

4. Other Control

4-1. Indoor Unit Self-Separator Oil Recovery Control
Refer to the indoor unit special control item.

5. Operation of Solenoid Valves

5-1. 4-way Valve Control
(1)
OFF conditions
At Cooling mode
Special control (reverse cycle start control, inter systems refrigerant oil recovery control, reverse cycle defrost
control) is in effect.
(2)
ON conditions
At Heating mode

6. Outdoor Unit Electronic Control Valve (Motor Valve) Control [MOV1]

1
6-1. Power Initialization
The valve position is 480 pulses if the indoor unit has not started once after the power was turned ON.
Operation of the electronic control valve during normal unit operation
Indoor Unit
Heat exchanger status
2
Condenser
Cooling
operation
Stop
Evaporator
Heating
operation
Stop
3
*
SH control controls the difference between outdoor heat exchanger liquid temperature and suction
temperature to 2 – 10°F.
4
5
6
MOV1
Maximum flow control
480
480
65 – Less than 480
SH (super heat) control
0
1 - 10
Mini ECO-i SYSTEM
Control Functions
Remarks