2-Way Air Discharge Semi-Concealed Type (S Type); Suspending The Indoor Unit - Sanyo SPW-X483GH56 Installation Instruction

Eco multi system air conditioner
Table of Contents

Advertisement

2-Way Air Discharge Semi-Concealed Type
(S Type)

3-5. Suspending the Indoor Unit

(1)
Place the full-scale diagram (supplied) on the
ceiling at the spot where you want to install the
indoor unit. Use a pencil to mark the drill holes.
2 2 2 2 2
Refer to Table 3-1 and Figs. 3-18 to 3-20.
S
NOTE
Since the diagram is made of paper, it may shrink or
stretch because of high temperature or humidity. For
this reason, before drilling the holes maintain the
correct dimensions between the markings.
(2)
Follow the diagrams to make the holes in the
ceiling.
Table 3-1
Length
A
Type
9, 12
960
18, 25
1,240
(3)
Depending on the ceiling type:
Insert suspension bolts as shown in Fig. 3-21.
or
Use existing ceiling supports or construct a
suitable support as shown in Fig. 3-22.
(4)
Cut the ceiling material, if necessary. (Refer to
Figs. 3-19 and 3-20, and Table 3-1.)
Unit : mm
B
C
D
330
1,070
640
330
1,350
640
Suspension lug
It is important that you use
extreme care in supporting
the indoor unit from the
ceiling. Ensure that the
ceiling is strong enough to
support the weight of the
unit. Before hanging the unit,
test the strength of each
attached suspension bolt.
Rear
117
Refrigerant
tubing side
Suspension bolt pitch A
Ceiling opening dimension C
Drain outlet
162
88
33
12
115
Optional cord outlet
Hole-in-anchor
Hole-in-plug
26
S4179544
Front face
Full-scale diagram
0035_T_I
Fig. 3-18
57
Suspension bolt
Fig. 3-19
Refrigerant connection outlet
(wide tube)
Refrigerant tubing cover
67
Refrigerant connection outlet
(narrow tube)
93
12
Power wiring outlet
Fig. 3-20
Concrete
Insert
Suspension bolt (M10 or 3/8")
(field supply)
Fig. 3-21
0038_T_I
Ceiling tiles
Ceiling support
Fig. 3-22
0039_S_I
0052_S_I
0053_S_I