Installing The Drain Piping - Sanyo SPW-X483GH56 Installation Instruction

Eco multi system air conditioner
Table of Contents

Advertisement

Fig. 3-87 shows an example of installation.
Air-outlet grille
3-27.

Installing the Drain Piping

(1) Prepare a standard hard PVC pipe (O.D. 32 mm)
for the drain and use the supplied hose band to
6 6 6 6 6
prevent water leaks.
The PVC pipe must be purchased separately.
U
When doing this, leave a gap between the drain
socket of the unit and the PVC pipe to allow the
drainage to be checked. The transparent drain
pipe allows you to check drainage. (Fig. 3-88)
CAUTION
(2) After connecting the drain piping securely, wrap
the supplied packing and drain pipe insulator
around the pipe, then secure it with the supplied
clamps. (Fig. 3-89)
NOTE
Make sure the drain pipe has a downward gradient
(1/100 or more) and that there are no water traps.
Air outlet duct
Ceiling material
Tighten the hose clamps so
their locking nuts face
upward. (Fig. 3-88)
Indoor unit
Fig. 3-87
Clamps (supplied)
Drain insulator (supplied)
44
S4179544
Bolt anchor
Suspension bolt
Air-intake duct
Air-intake grille
0785_U_I
Hose band (supplied)
Hard PVC pipe
(not supplied)
gap
Packing (supplied)
Transparent drain pipe
To be installed
at the site
0774_X_I
Fig. 3-88
Clamps (supplied)
0046_X_I
Fig. 3-89