Adapting To Another Gas; Changing The Burner Injectors - DeDietrich DTG 320 Eco.NOx Series Manual

Adapting to another gas
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 13
DTG 320 Eco.NOx / DTG 330 Eco.NOx
GD 66-74 + 86-94 + 207

Adapting to another gas

Boilers DTG 320-... Eco.NOx
Boilers DTG 330-... Eco.NOx
Natural gas L/LL
Natural gas H/E
Propane
These actions must be carried out by a qualified
technician.

1 Changing the burner injectors

8
9
GD66
GD67
GD86
GD87
GD207
GD207
94858180
10
11
12
GD68
GD69
GD70
GD88
GD89
GD90
GD207
GD207
GD207
The 300-mbar versions cannot be converted to propane.
Cut the electricity and gas supply to the boiler.
+
Lift out the injector with a number 12 spanner assemble the
new injectors with their new joint.
Natural gas H/E
Natural gas L/LL
Propane
Assembly:
Correctly replace the seals.
First tighten the injectors by hand and carefully lock them using
a spanner.
Carry out a gas tightness check.
Pressure socket
14
16
18
GD71
GD72
GD73
GD91
GD92
GD93
GD207
GD207
GD207
Nozzle
Injector marking
Ø 3.6 mm
Ø 4.35 mm
Ø 2.20 mm
English
01/10/07
20
GD74
GD94
GD207
360 B
435 B
220 B

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dtg 330 eco.nox series

Table of Contents