Table 1 - Descriptions Of Major Components (Figure 4) - Honeywell HC900 Installation And User Manual

Process controller
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

Components and Architecture - Components
Key No.
Component
Name
1
Controller
(Local) Rack
2
I/O Expansion
Rack
(C50/C70 CPU
only)
3
Operator
Interface
4
PC
Configuration
Tool
5
HMI (Human-
Machine
Interface)
6
Ethernet
100Base-T
Switch
6a
Ethernet
10/100Base-T
Switch or
Router
7
Ethernet CAT5
shielded cable
Fiber Optics
Cable
8
Ethernet CAT5
shielded cable
IO
9
RS-232 cable
10
RS-485 to
USB converter
Revision 19
06/14
Table 1 – Descriptions of Major Components (Figure 4)
Description
Includes: Rack, Power Supply, Controller Module,
and I/O modules
(Optional) Includes: Rack, Power Supply, Scanner
Module, and I/O modules
900 Control Station operator interface communicates
via Ethernet or RS-485 serial link
For legacy system- The PC configuration tool
connects from the RS-232 serial port of the
Controller Module to a serial port on the PC
For new system – The PC Configuration tool
connects from the RS-485 port of the Controller
Module using an external Honeywell qualified RS-
485 to USB converter.
(Optional) PC link to Ethernet network, which may
include other HMIs, other HC900 Controllers, and
other networks (including Internet).
Typically includes HMI operating software.
May also include Designer Software (configuration
tool and utility software).
Enables connection of the private Ethernet 100Base-
T port on a Controller Module to the Scanner
modules on 2, 3, or 4 I/O Expansion racks. (C50/C70
CPU only) (If a single I/O expansion rack is
connected directly to a Controller Module, the Switch
is not required.)
Enables inter-connection of several 10/100Base-T
Ethernet devices in an Ethernet network. Devices
include other HC900 Controllers, HMIs, and can also
include routers, brouters, servers, and other devices
in wider networks.
Connects I/O expansion racks (C50/C70 CPU only)
to controllers and/or to 10/100baseT Ethernet
switches. 10'or 20' (3.04 or 6.08m)
Controller to remote rack distance up to 750m (2460
ft.) with one fiber cable. Distances up to 1500m (4920
ft.) are possible with a fiber switch used as a repeater
at the midpoint.
Connects devices in Ethernet Open Connectivity
network to 900 Control Stations and PC SCADA
applications.
For legacy system, Null modem cable, up to 50'
(15.24m) (PC modem cable if used with Modems.)
Connects RS-485 port to USB port.
HC900 Process Controller Installation and User Guide
Source
Honeywell
Honeywell
Honeywell
PC is from third-party
supplier. Configuration
software is from Honeywell.
PC is from third-party
supplier. HMI software is
available from Honeywell
(PlantScape or
SpecView32) or from third-
party supplier.
Honeywell
Third-party suppliers.
Third-party suppliers or
Honeywell
Third-party suppliers or
Honeywell
Third-party suppliers or
Honeywell
Third-party suppliers or
Honeywell
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents