Communications Installation - Connecting the HC900 Controller to a PC with the Designer Software
Best Data 56SX Data Fax External Modem
Step
1
Connect the modem to a PC. If your PC's RS-232 port has a 2- pin connector, use a DB-9
male to DB-25 female modem cable. If your PC's RS-232 port has a 9-pin connector, use a
DB-9 male to DB-9 female RS-232 cable.
2
Connect power to the modem.
3
Power-up the modem.
4
Run a serial communication port program such as Hyperterminal.
5
Within the communication program, select the port to which the modem is connected.
6
Configure the port to these settings:
configured in HC900 Controller)
7
In the program's terminal window, restore factory defaults by keying-in the following command
string:
AT &F0
Then, press the ENTER key.
8
In the program's terminal window, key-in in the following command string:
AT E1 Q0
Then, press the ENTER key. The modem should give an
9
Key-in the following command string:
AT &C0 &D0 &K0 &R1 &S0 &Y0 S0=1
The Modem should respond with
10
Key-in the following command string:
AT E0 Q1 &W0
The Modem will not respond.
11
Power down the modem and disconnect it from the PC.
12
Connect the modem's serial cable to the?
13
Connect the modem to a telephone jack.
14
Power up the modem and the HC900 Controller.
15
On a remote computer, run Designer software.
16
Set up the PC software to dial the HC900 Controller.
17
Use the PC software "Loop-back" feature to verify that communications are established with
the remote HC900 Controller.
Revision 19
06/14
baud rate = 1200, 2400, 4800, 9600, 19200, 38400, 57600 (Must match Baud Rate
data bits = 8
parity = none
stop bits = 1
flow control = none
OK