Appendix - Installation of Remote Termination Panels (RTPs) - Analog Input/Digital Input/Digital Output/Analog
Output
8 Point Analog Output
Step
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
Mount RTP cable assembly to HC900 Controller (Figure 92).
Remove appropriate key tabs from terminal board to allow mating with the module. See page 75.
Connect terminal block end of desired cable assembly to 8 point Analog Output module at controller.
Choose from:
900RTC-B810
900RTC-B825
900RTC-B850
Install 8 point Analog Output label into the module connector cover.
Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring
shields must be grounded as described in the shield grounding section (page 70).
2
Mount RTP to DIN rail.
Latch to rail. See page 244.
Connect cable to RTP.
3
Set/verify jumper positions on each RTP as shown.
Module Removal / Insertion Under Power (RIUP) is supported by turning off Switch SW1 to allow removal of
the module from the rack without causing an arc. See page 73.
ATTENTION: SW1 opens the + side of the External 24V Power so that RIUP of module is possible.
See page 233 for RTP internal schematic.
Revision 19
06/14
Remote Terminal Cable assembly, 1.0 meters long
Remote Terminal Cable assembly, 2.5 meters long
Remote Terminal Cable assembly, 5.0 meters long
HC900 Process Controller Installation and User Guide
Action
Jumper open
Jumper closed
231