Honeywell HC900 Installation And User Manual page 234

Process controller
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

Appendix - Installation of Remote Termination Panels (RTPs) - Analog Input/Digital Input/Digital Output/Analog
Output
16 Point Contact Digital Input
Step
4
Connect field wiring.
16 Point DC Digital Input
Step
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
ATTENTION: The RTP combines the two groups of 8 inputs into one group of 16.
Mount RTP cable assembly to HC900 Controller (Figure 92).
Remove appropriate key tabs from terminal board to allow mating with the module. See page 75.
Connect desired cable to 16 point DC DI module at controller. Choose from:
900RTC-L010
900RTC-L025
900RTC-L050
Install 16 point DC DI module label into the module connector cover.
Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring
shields must be grounded as described in the shield grounding section (page 70).
2
Mount RTP to DIN rail.
Latch to rail. See page 244.
Connect cable to RTP.
222
1
2
3
4
5
6
7
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
Remote Terminal Low Voltage Cable Assembly, 1.0 meters long
Remote Terminal Low Voltage Cable Assembly, 2.5 meters long
Remote Terminal Low Voltage Cable Assembly, 5.0 meters long
HC900 Process Controller Installation and User Guide
Action
8
9 10 11 12 13 14 15 16 17 18 19 20
Install jumper wires
Action
Revision 19
06/14