Removal and Replacement Procedures - Safety Considerations - PLAN AHEAD!
Battery Replacement Procedures
Step
1.
applied, the content of SDRAM will be lost.
Before beginning this procedure, upload and SAVE a copy of the configuration, or ensure that a
previously saved copy of the current configuration is available.
2.
Apply site AC power to the Power Supply that is associated with the controller Module..
3.
Press the latch on the battery cover (1) to release
the battery holder, and pull on the handle (2) to
remove the battery holder.
Note the orientation of the battery-holder assembly
(battery toward the left).
4.
The battery is retained in the holder by spring
tension of the plastic holder itself.
Extract the battery from the holder by using your
thumb to apply pressure to the front end of the
battery, and rotating it to the left.
Insert the negative end of the new battery into the
back end of the holder, and press on the battery so
that it snaps into the holder.
To ensure that the battery is seated properly, rotate
it in the holder, using finger or thumb pressure
toward the positive (front) end of the battery.
5.
While maintaining proper orientation (battery toward the left), slide the battery holder into the
slot in the Controller Module until it snaps into place.
Revision 19
06/14
Table 40 – Replacing a Backup Battery (CPU Powered))
If the battery is removed from the Controller Module when AC power is not
HC900 Process Controller Installation and User Guide
Action
193