9 RELAY COMMISSIONING
ENERVISTA MII SETUP HMI
General Settings
ADV. GENERAL
(Adv.)
SETTINGS
Identification
IDENTIFICATION
Active Group
Settings group
Trip Contact -
Trip Min Time
Minimum time closed.
Ph TOC Funct. group
Phase TOC 51P (group
2
2)
51P Permission to
Trip Enable 51P
Trip
51P Pickup Value
Pickup 51P
51P Curve Type
Curve 51P
51P Time Dial
TD mult 51P
51P Definite Time
Def Time 51P
Delay
Gnd TOC Fun. group
Ground TOC 51G
2
(group 2)
51G Permission to
Trip Enable 51G
Trip
51G Pickup Value (1/
Pickup 51G
5 A ground)
51G Pickup Value
Pickup 51G
(sensitive ground)
51G Curve Type
Curve 51G
51G Time Dial
TD mult 51G
51G Definite Time
Def Time 51G
Delay
Ph IOC High Set
PHASE IOC 50P1
group 2
(group 2)
50P1 Permission to
Trip Enable 50P1
Trip
50P1 Pickup
Pickup 50P1
50P1 Time Delay
Delay 50P1
Ph IOC Low Set
PHASE IOC 50P2
group 2
(group 2)
50P2 Permission to
Trip Enable 50P2
Trip
50P2 Pickup
Pickup 50P2
50P2 Time Delay
Delay 50P2
Gnd IOC High Set
GROUND IOC 50G1
group 2
(group 2)
50G1 Permission to
Trip Enable 50 G1
Trip
GEK-106237P
USER
SETTING
GENERAL
ADVANCED
---
Settings Group
Trip Min Time
PHASE TOC 51P
Trip Enable 51P
Pickup 51P
Curve 51P
TD mult 51P
Def Time 51P
GROUND TOC 51G
Trip Enable 51G
Pickup 51G
Pickup 51G
Curve 51G
TD mult 51G
Def Time 51G
Phase IOC 50P1
Trip Enable 50P1
Pickup 50P1
Delay 50P1
Phase IOC 50P2
Trip Enable 50P2
Pickup 50P2
Delay 50P2
Ground IOC 50G1
Trip Enable 50 G1
MIFII Digital Feeder Relay
9.19 USER SETTINGS

9.19.2 ADVANCED SETTINGS

RANGE
Text
1 / 2
50 – 300 ms.
Yes/No
0.1 – 2.4 In (Ph)
DEFINITE TIME, USER, MOD
INVERSE, VERY INVERSE, EXTR
INVERSE, INVERSE LONG, INVERSE
SHORT
0.05 – 2.00
(IEC curves)
0.5 – 20.0
(ANSI curves)
0.5 – 10.0
(IAC curves)
0.00 – 600.00 s.
Yes/No
0.10 – 2.40 In (Gnd)
0.005-0.12 A
DEFINITE TIME, USER, MOD
INVERSE, VERY INVERSE, EXTR
INVERSE, INVERSE LONG, INVERSE
SHORT
0.05 – 2.00
(IEC curves)
0.5 – 20.0
(ANSI curves)
0.5 – 10.0
(IAC curves)
0.00 – 600.00 s
Yes/No
0.1 – 30 In (Ph)
0.00 –600.00s.
Yes/No
0.1 – 30 In (Ph)
0.00 –600.00s.
Yes/No
STEP
NA
NA
1 ms.
NA
0.01 In
(P)
NA
0.01
0.01
0.01
1.00 s.
NA
0.01 In
(G)
0.001 A
NA
0.01
0.01
0.01
0.01 s
NA
0.1 In
(Ph)
0.01 s.
NA
9
0.1 In
(Ph)
0.01 s.
NA
9-29