Description Of The Connectors / Interfaces - LinMot E100 Series Installation Manual

Table of Contents

Advertisement

Controller Series E100/200/400

Description of the connectors / Interfaces

1 PWR Signal+
2 GND
3 PWR Motor+
LED
Fault
Ready
Stat A
Stat B
NTI AG
Power Supply
Power Connector
GND internally
connected to
controller housing
must be externally connected
to earth (Ground Bus)
Supply:
Supply Voltage 24...48VDC. Absolute max. Rating 48VDC + 10%
Supply voltage for PWR Signal and PWR Motor may be different
Motor Supply GND must be externally connected to earth
Caution:
By exceeding 53VDC supply voltage, the controller will go into error state. Voltage higher than 55 VDC
will damage the controller!
Do not switch Power Supply DC Voltage. All power supply switching and E-Stop breaks should be
done to the AC supply voltage of the power supplies
Power supply connectors must not be connected or disconnected while DC voltage is present.
Wiring:
1.5 mm² (AWG16), max length 5 m
State Display
Ready Green
READY
The system has started correctly
Stat A Yellow
STAT A
Coding for the actual operating state
Stat B Yelllow
STAT B
Coding for the actual operating state
The display of the various operating states is shown on the last page of this manual..
FAULT
An error has occurred
Fault red
(In the state ERROR a blink code of the STAT LEDs A and B tells what the actual
error is. The blink codes are explained in chapter 'Service'of the user Manual.)
Installation: E100/E200/E400 series / 28.07.2010
GND
24...48VDC
24...48VDC
Internal
Internal
Fuse 500mAT
Fuse 10AT
1 2 3
24...48VDC
24...48VDC
Supply GND
Page 6/12