Inverter Error - Fujitsu Airstage V-II Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V-II:
Table of Contents

Advertisement

Trouble shooting 21
OUTDOOR UNIT Error Method:

Inverter Error

Detective Actuators:
Inverter PCB
Forecast of Cause :
1. Noise, momentary open, voltage drop. 2. Power supply to Filter PCB (INV) to Inverter PCB
wiring disconnection, open 3. Filter PCB ( INV) defective 4. Inverter PCB defective
5. Cement Resistor Open circuit
Check Point 1-1 : Turn the power
on again.
Error displayed again?
YES
Check Point 2 : Check the wiring (Power supply to Filter PCB (INV) to Inverter PCB)
Connector and wiring connection state check
Cable open check
OK
Check Point 3 : Check Cement resistor
Check resistance of cement resistor
If the circuit of both terminal was open circuit, exchange the Resistor
Correct resistance value: 5.3 - 6.0 Ohm
OK
Check Point 4 : Check Filter PCB (INV) and Inverter PCB
Check Filter PCB (INV) and Inverter PCB.
(Refer to "Sarvise Parts Information 5")
Indicate or Display:
Outdoor Unit : E. 63. 1
Indoor Unit
: Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Error Code
: 63
Detective details:
Error information received from Inverter PCB
Check Point 1-2 : Noise, momentary open, voltage drop
NO
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the
power line.
04-29