Sub-Cool Heat Ex. Gas Outlet Temp Sensor Error - Fujitsu Airstage V-II Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V-II:
Table of Contents

Advertisement

Trouble shooting 35
OUTDOOR UNIT Error Method:
Sub-cool Heat EX. Gas outlet
Temp Sensor Error
Detective Actuators:
Sub-cooling heat exchanger gas outlet
temperature thermistor
Forecast of Cause :
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 22".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN142:7-8) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Sub-cooling heat exchanger gas outlet temperature sensor (CN142:7-8)
If the voltage does not appear, replace Main PCB and set up orignal address.
(Refer to 06-03 page Main PCB removal.)
Indicate or Display:
Outdoor Unit : E. 82. 2
Indoor Unit
Error Code
Detective details:
Sub-cooling heat exchanger gas outlet temperature thermistor short or
open detected
CN142
: Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
: 82