Fujitsu Airstage V-II Service Manual page 180

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V-II:
Table of Contents

Advertisement

Check Point : ARXB14LALH (Compact Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
140°C
Pr
Check Point : ARXB18LALH (Compact Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
150°C
Pr
BLUE (S-Lo)
VIOLET (Low)
PINK (Med)
RED (Hi)
(AC)
BLACK
WHITE
BLUE (S-Lo)
VIOLET (Low)
PINK (Med)
RED (Hi)
(AC)
BLACK
WHITE
04-118
Lead wire
Resistance value
White Red
136.5
Red
Black
125.6
Red
Pink
23.7
Pink
Violet
23.7
Violet
Blue
49.4
Lead wire
Resistance value
White Red
89.7
Red
Black
150
Red
Pink
37.4
Pink
Violet
37.4
Violet
Blue
197
8%
8%
8%
8%
8%
at 20°C
8%
8%
8%
8%
8%
at 20°C