2-12. E: 63. Inverter error (Outdoor unit)

Indicator
Indoor unit
Detective actuator
Outdoor unit
Forecast of cause
Check point 1. Turn the power on again?
Error displayed again?
Check point 2. Check the wiring (power supply to inverter PCB)
Connector and wiring connection state check
Cable open check
Check point 3. Replace inverter PCB
Replace inverter PCB
Check point 1-2. Check external cause
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the power line.
2-12. E: 63. Inverter error (Outdoor unit)
Operation indicator
Timer indicator
Economy indicator
Error code
Inverter PCB
End
End
Continuous flash
Error information received from inverter PCB
External cause
Power supply to inverter PCB wiring disconnection or
Inverter PCB failure
If no, go to
"Check point
- (03-23) -
6 time flash
3 time flash
E: 63
open
1-2".