Precautions For Exchange Of Refrigerant-Cycle-Parts - Fujitsu Airstage V-II Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V-II:
Table of Contents

Advertisement

17. Precautions for exchange of refrigerant-cycle-parts

(1) During exchange the following parts shall be protected by wet rag and not make the allowable temperature or more.
(2) Remove the heat insulation when there is the heat insulation near the welding place.
Move and cool it when its detaching is difficult.
(3) Cool the parts when there are parts where heat might be transmitted besides the replacement part.
(4) Interrupt the flame with the fire-retardant board when the flame seems to hit the following parts directly.
(5) Do not allow moisture or debris to get inside refrigerant pipes during work.
(6) When brazing, be sure to replace the air in the pipe with nitrogen gas to prevent forming oxidization scale.
SOLENOID VALVE 1 /2 /3
SOLENOID VALVE 5
SOLENOID VALVE 6
EXPANSION VALVE 1 /2
4WAY VALVE
CHECK VALVE
3WAY VALVE (GAS)
3WAY VALVE (LIQUID)
RELIEF VALVE
UNION JOINT
HIGH PRESSURE SENSOR
LOW PRESSURE SENSOR
PRESSURE SWITCH
Allowable
Part name
temperature
200°C
120°C
120°C
120°C
100°C
120°C
100°C
100°C
100°C
Precautions in work
Remove the coil before brazing.
And install the coil after brazing.
Remove the coil before brazing.
And install the coil after brazing.
Remove the suction temp. sensor before brazing.
And install the suction temp. sensor after brazing.
Remove the pressure sensor before brazing.
And install the pressure sensor after brazing.
Tighten the flare part gripping it.
+ -
(Tightening torque :15 1.5N m)
Do the static electricity measures.
06-12
Applicable
Outdoor unit (HP)
08 10 12 14 16
.