SERVICE PARTS INFORMATION 10

Resistor, Cement

Check Point 1 : Appearance check
No fissures, breaks, damage, etc. at the body and terminals section?
Check Point 2 : Electric check
1. Surge prevention resistor (connected to magnetic contactor)
Set the tester to the "Resistance" mode, and measure the resistance value between the terminals.
(No polarity)
Judge the result of
5.32
to 5.88
Other than the above : Deteriorated, defective
2. Balance resistor (connected to electrolytic capacitor)
Set the tester to the "Resistance" mode, and measure the
resistance value between the terminals. (No polarity)
Judge the result of
31.35
to 34.65
Other than the above : Deteriorated, defective
SERVICE PARTS INFORMATION 11
Capacitor
Check Point 1 : Appearance check
Explosion-proof not operated?
Electrolyte not leaking?
No abnormalities at threaded parts? (Stripped threads, deformation, damage, etc.)
Check Point 2 : Electric check
No short between terminals?
as follows:
: Normal
as follows:
: Normal