Pcb Error 1 - Fujitsu Airstage V-II Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V-II:
Table of Contents

Advertisement

3. Network Convertor (UTY-VGGX)
1. When connecting a group remote controller to a network convertor
Trouble shooting 79
Error Contents :
Power Supply Error
Details :
Condition of occurrence : Normal power is not supplied. 7 segment indicator is defective.
Release condition : Normal power is supplied. 7 segment indicator is normal.
Cause 1 :
Power supply cable installation is defective or open.
Check following installation and reset the power supply.
(1) Installation of power cable on power supply terminal.
(2) Connection between Power PCB and Terminal.
(3) Connector condition between power PCB and Main PCB.
Trouble shooting 80
Error Contents :

PCB Error 1

Details :
Condition of occurrence : Synchronization of Network Device was not normally done.
Release condition : When the synchronization of the device is normally done.
Cause 1 : External noise
After pressing SW104 of Network Convertor PCB for 5 seconds or turning on power.
Does error code display reappear?
YES
Remove the surrounding noise source.
OK
Cause 2 : Network Convertor is defective.
Replace Network Convertor.
-
Symptom :
No display
Symptom :
Error Code display [ C 1 ]
All the control items do not operate.
OK
Cause 2 : Network Convertor is defective.
If normal voltage (220V) is applied to power supply
terminal of Network Convertor, there is a possibility of
defective PCB. Proceed as follows.
Replace Nerwork Convertor.
NO
It is not a defect of PCB. Remove the surrounding noise source.
04-80