Incompatible Indoor Unit Is Connected - Fujitsu Airstage V-II Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V-II:
Table of Contents

Advertisement

Trouble shooting 98
Error Contents :
Incompatible Indoor Unit is
Connected
Details :
Condition of occurrence : When information was not obtained from indoor unit
Release condition : When information was obtained from indoor unit
Cause 1 : Check remote controller master/slave setting.
For the check and modification methods, refer to the remote controller (including external
SW) installation manual.
When there is 1 remote controller, check whether or not it is set as the master remote
controller.
When there are 2 remote controllers, check if one side is the master remote controller and
the other side is the slave remote controller.
When there are 1 remote controller and 1 external switch controller, check if the remote
controller is master controller and the external switch controller is slave controller.
OK
Cause 2 : Check connection
Check cable
Check indoor unit power supply
OK
Cause 3 : Noise
Source around cable
OK
Cause 4 : Remote controller trouble
Replace remote controller.
OK
Cause 5 : Indoor unit PCB trouble
Change Controller PCB and set up the original address.
(Refer to 06-03 page Main PCB removal.)
Symptom :
Error Code display [ 1 5 ]
or unit
04-93