Inverter Pcb Momentary Power Failure Detection - Fujitsu Airstage V-II Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V-II:
Table of Contents

Advertisement

Trouble shooting 22
OUTDOOR UNIT Error Method:
Inverter PCB Momentary Power
Failure Detection
Detective Actuators:
Inverter PCB
Forecast of Cause :
1. Noise, momentary power failure, voltage drop 2. Magnetic Relay (for Inverter) coil side
wiring disconnection, open 3. Power supply to Filter PCB (INV) to Inverter PCB wiring
disconnection, open 4. Main PCB defective 5. Inverter PCB defective
Check Point 1 : Noise, momentary power failure, voltage drop
Check if temporary voltage drop was not generated.
Check if momentary power failure was not generated.
Check if ground is connection correctly or there are no related cables near the power line.
OK
Check Point 2 : Check the magnetic contactor (for Inverter) coil side wiring
Connector and wiring connection state check
Cable open check
OK
Check Point 3 : Check the wiring (Power supply to Filter PCB (INV) to
Inverter PCB)
Connector and wiring connection state check
Cable open check
OK
Check Point 4 : Check Main PCB
Chack Main PCB. (Refer to "Sarvise Parts Information 4")
>>If replace Main PCB, Refer to 06-03 page Main PCB removal.
OK
Check Point 5 : Replace Inverter PCB
Replace Inverter PCB.
Indicate or Display:
Outdoor Unit : E. 67. 2
Indoor Unit
: No Display
Error Code
: 67
Detective details:
''Momentary power failure" received from Inverter PCB