SERVICE PARTS INFORMATION 7
CT PCB
Check Point 1
Measure the AC current flowing from TM302 and the DC voltage between connector
pins 1-3 at that time.
AC current
AC
TM302
TM301
CN302
1
3
CT PCB
DC
AC current - DC voltage characteristic
DC voltage [V]
2.45
10
0
AC current [A]
04-104