Fujitsu Airstage V-II Service Manual page 179

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V-II:
Table of Contents

Advertisement

Check Point : ARXB07LALH (Compact Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
140°C
Pr
Check Point : ARXB09LALH (Compact Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
140°C
Pr
Check Point : ARXB12LALH (Compact Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
140°C
Pr
BLUE (S-Lo)
VIOLET (Low)
PINK (Med)
RED (Hi)
BLACK
(AC)
WHITE
BLUE (S-Lo)
VIOLET (Low)
PINK (Med)
RED (Hi)
(AC)
BLACK
WHITE
BLUE (S-Lo)
VIOLET (Low)
PINK (Med)
RED (Hi)
BLACK
(AC)
WHITE
04-117
Lead wire
Resistance value
White Red
579
255
Red
Black
162
Red
Pink
Pink
Violet
66
Violet
Blue
93
Lead wire
Resistance value
White Red
322.8
255
Red
Black
Red
Pink
103
Pink
Violet
53
Violet
Blue
100.7
Lead wire
Resistance value
White Red
336
261
Red
Black
107
Red
Pink
Pink
Violet
55
Violet
Blue
103
8%
8%
8%
8%
8%
at 20°C
8%
8%
8%
8%
8%
at 20°C
8%
8%
8%
8%
8%
at 20°C

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents