2-7. E: 32. Indoor unit main PCB error (Indoor unit)

→ired remote
Indicator
controller
Detective actuator
Indoor unit
Forecast of cause
Check point 1. Reset power supply and operate
Does error indication show again?
If no, go to
"Check point
Check point 2. Check Indoor unit electrical components
Check all connectors. (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
Check point 3. Replace the main PCB
Replace the main PCB.
Check point 1-2. Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light
bulb or any electronic equipment which causes harmonic wave).
NOTE: EEPROM
EEPROM (Electronically Erasable and Programmable Read Only Memory) is a non-volatile
memory which keeps memorized information even if the power is turned off. It can change
the contents electronically. To change the contents, it uses higher voltage than normal, and
it cannot change a partial contents. (Rewriting shall be done upon erasing the all contents.)
There is a limit in a number of rewriting.
2-7. E: 32. Indoor unit main PCB error (Indoor unit)
Error code
Main PCB
1-2".
End
End
→hen power is on and there is some below case.
1. →hen model information of EEPROM is incorrect.
2. →hen the access to EEPROM failed.
External cause
Defective connection of electrical components
Main PCB failure
- (03-13) -
E: 32