WARNING
Hydrogen and oxygen gases are emitted from batteries into the surrounding atmosphere
during charge, float charge, heavy discharge, and overcharge. Explosive gas mixture may
be created if the hydrogen concentration exceeds 4% by volume in air. Necessary air flow
rate for ventilation of UPS location must be ensured. A minimum air flow is 1.3 m³/ hour
for the room where one 93PM UPS with internal VRLA batteries is placed. If more than one
UPS with internal VRLA batteries are located in the same room, ventilation air flow must
be dimensioned accordingly. If external flooded cell batteries are used in same location,
ventilation air flow must be recalculated and dimensioned accordingly.