1. For UL Residential Burglar Alarm installations with line security, total exit delay time must not
exceed 60 seconds. For UL Burglar Alarm installations without line security, total exit delay time
must not exceed 120 seconds.
2. Periodic testing (see scheduling mode) must be at least every 24 hours.
3. Remote downloading without an alarm company technician on-site (unattended downloading) is not
permissible for UL installations.
4. Auto-disarming is not a UL Listed feature.
5. As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial and
residential applications, the following UL requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a signal to a
remote monitoring location, or to delay the energizing of a local alarm sounding device to permit the
alarm system user to enter and disarm the system, or to arm the system and exit shall not exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system without standard line security or encrypted line security, or
c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.
1. Report Alarms: Default is "Enabled"
2. Report Troubles: Default is "Enabled"
3. Exit Error: Default is "Enabled".
4. Recent Closing: Default is "Enabled".
7. Alarm Cancel: Default is "Enabled".
5. Call Wait Cancel: If call waiting is used, a call waiting cancel prefix must be entered.
6. Swinger Shutdown: Options for "alarm sounding per zone" include 1 report or 2 reports. Default is "2
Reports".
7. Abort Window: Options include 15, 30 and 45 seconds. Default is 30 seconds.
8. Entry Delay 1 and 2: Options include 30, 45, 60 and 90 seconds and 2, 3 or 4 minutes. Minimum entry
delay is 30 seconds. When added together the entry delay plus the dialer delay should not exceed 1
minute.
9. Exit Delay: Options include 45, 60, 90 seconds and 2 minutes. Minimum exit delay is 45 seconds.
10. Restart Exit Time: Default is "Yes".
11. Exit Warning: Always enabled. This field is not programmable
12. Auto Stay Arming: Default is "Yes".
13. Cross Zone Delay: Options include None or selections between 30 seconds and 2 minutes (in 30 second
increments), 3 minutes and 4 minutes. Default is 3 minutes.