Fan Module - Oracle Sun ZFS Service Manual

Storage 7x20 appliance customer
Table of Contents

Advertisement

2. If you are not physically at the system, turn on the locator indicator by clicking the locator
icon
.
3. Push the release button on the HDD or SSD to open the latch.
4. Grasp the latch (2), and pull the drive out of the drive slot.
5. After 15 seconds, navigate to the Hardware > Maintenance screen, and click the details icon
on the system controller to verify that the software has detected that the drive is not
present.
6. Slide the replacement drive into the slot until it is fully seated.
7. Close the latch to lock the drive in place.
The Sun ZFS Storage system software automatically detects and configures the new drive.
The device appears in the BUI Maintenance > Hardware screen when you view details for
the controller, drive shelf or cage.

Fan Module

Fan modules are hot-swappable and can be removed and installed while the storage controller is
running without affecting other hardware capabilities.
Caution: Operating a controller for an extended period of time with fans removed reduces the
effectiveness of the cooling system. For this reason, the replacement fan should be unpacked in
advance and ready to insert into the controller chassis as soon as the faulted fan is removed.
Chapter 2 • Hardware Maintenance
7x20
55