Side Vent Configuration with Vertical Termination

The termination must fall
within the shaded area
shown in the chart. Use
the indicated restrictor
and diffuser positions.
Up to four elbows (45°
or 90°) may be used.
Only one horizontal
elbow may be used.
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
© Travis Industries
Installation
(for qualified installers only)
40' max (12m)
35 feet (10.5m)
30 feet (9m)
25 feet (7.5m)
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
H1
4121105
Exhaust Restrictor # 4
Intake Restrictor # 2
Diffuser Position # 1
Exhaust Restrictor # 2
Intake Restrictor # 1
Diffuser Position # 1
H2
Horizontal length is calculated by adding
both lengths of horizontal run
(Horizontal Length = H1 + H2).
This is considered a
vertical elbow