Wiring For Proprietary Security Alarm Applications - Notifier NFS-640 Installation Manual

Fire alarm control panel
Hide thumbs Also See for NFS-640:
Table of Contents

Advertisement

Applications

4.4.5 Wiring for Proprietary Security Alarm Applications

Typical wiring for proprietary security alarm applications with FCM-1 modules or XP5-M
modules. Note the following:
• The module is programmed with software
• Supplementary use only applies to UL-listed systems.
• NAC devices used for security cannot be shared with fire NAC devices.
• Refer to the Device Compatibility Document for compatible NAC devices.
• All monitor modules used for security application must be installed in the NFS-640 cabinet
with STS-1 Security Tamper Switch.
Figure 38 Wiring Diagram for Proprietary Security Alarm Applications
UL-listed 47K
End-of-Line Resistor
(provided with module)
NFS-640 Protected Premises Unit
SLC
(+)
Channel
(-)
A or B
14
12
13
62
UL-listed,
normally-open
security switch
UL-listed, normally-closed
security switch
B-
B+
B-
B+
B-
B+
B+
B-
B+
SW101
SW 201
SW202
SW302
SW402
0
1
5
SW1
XP5-M
Type Code.
SECURITY
NFS-640 Protected Premises Unit
9
0
7
8
9
6
10
5
11
4
8
1
12
3
13
2
1
14
0
15
7
2
TENS
7
8
6
9
5
6
3
4
3
2
1
5
4
0
ONES
ADDRESS
LOOP
FCM-1
UL-listed,
normally-open
security switch
UL-listed, normally-closed
security switch
UL-listed,
normally-open
security switch
UL-listed, normally-closed
security switch
NFS-640 Installation Manual P/N 51332:B1 12/01/2003
Fire/Security Applications
SLC
Channel
A or B
+
UL-listed
47K
End-of-Line
Resistor
(provided
with module)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents