Installing the Control Panel
Mount single-space blank plate
onto compatible dress panel or
backbox trim ring
WARNING: Remove all power sources to equipment while connecting electrical components.
!
Leave the external, main power breaker OFF until installation of the entire system is complete.
WARNING: Several sources of power can be connected to the control panel. Before servicing the
!
control panel, disconnect all sources of input power including the battery. While energized, the
control panel and associated equipment can be damaged by removing and/or inserting cards,
modules, or interconnecting cables.

3.5.6 Overview

Complete all mounting procedures and check all wiring before applying power. Electrical
connections include the following:
• Primary AC power source – 120 VAC, 50/60 Hz, 3.0 A (NFS-640E uses 240 VAC, 50/60
Hz, 1.5 A) from line voltage source. Overcurrent protection for this circuit must comply
with Article 760 of the National Electrical Code (NEC) and/or local codes. Use 12 AWG
(2.00 mm
• Secondary power source – 24 VDC from batteries, installed in the control panel (or in an
optional battery cabinet). Secondary (battery) power is required to support the system
during loss of primary power.
• External power sources – 24 VDC power for Smoke Detectors (4 wire), NACs, and
Annunciators.
See Appendix B "Electrical Specifications" for details and overall installation guidelines.

3.5.7 Connecting the Control Panel to AC Power

Connect primary power as follows (see Figure 14 below):
1.
Turn off the circuit breaker at the main power distribution panel.
2.
Remove the plastic insulating cover from TB2.
3.
Connect the service ground to terminal marked EARTH.
4.
Connect the primary neutral line to terminal marked NEUTRAL and the primary Hot line to
terminal marked HOT.
5.
Reinstall the plastic insulating cover over TB2.
NFS-640 Installation Manual P/N 51332:B1 12/01/2003
Figure 13 Mounting Single-space Blank Plate with Optional Module
Connecting the Power Cables
Single-space
blank plate
Mount optional module
onto standoffs on the
blank plate
2
) wire (maximum) with a 600-volt rating.
Installation
Fasten optional module to
the plate with four screws
(included).
37