Section 4 Applications

4.5.6 Wiring for Proprietary Security Alarm Applications

Typical wiring for proprietary security alarm applications with the FMM-1 module.
Note the following:
• The module is programmed with one of five type codes (see Section 4.5.2 "General Security
Requirements").
• Supplementary use only applies to UL-listed systems.
• NAC devices used for security cannot be shared with fire NAC devices.
• Refer to the Device Compatibility Document for compatible NAC devices.
• All monitor modules used for security application must be installed in the control panel cabinet
with STS-1 Security Tamper Switch.
47K
End-of-Line
Resistor
NFS-3030 Protected Premises Unit
SLC
(+)
Channel
(-)
A or B
14
12
13
52
Figure 37 Wiring Diagram for Proprietary Security Alarm Applications
UL-listed,
normally-open
security switch
UL-listed, normally-closed
security switch
B-
B+
B-
B+
B-
B+
B+
B-
SW101
SW 201
SW202
SW302
SW402
0
1
5
SW1
XP5-M
NFS-3030 Protected Premises Unit
9
0
7
8
9
6
10
5
11
4
8
1
12
3
13
2
1
14
0
15
7
2
TENS
7
8
6
9
5
6
3
4
3
2
1
5
4
0
ONES
ADDRESS
LOOP
FMM-1
UL-listed,
normally-open
security switch
B+
UL-listed, normally-closed
security switch
UL-listed,
normally-open
security switch
UL-listed, normally-closed
security switch
NFS-3030 Installation PN 51330:C 10/28/2003
Fire/Security Applications
SLC
Channel
A or B
+
47K
End-of-Line
Resistor