5: Wiring For Proprietary Security Alarm Applications - Notifier NFS2-640/E Installation Manual

Fire alarm control panel
Hide thumbs Also See for NFS2-640/E:
Table of Contents

Advertisement

Applications
4.6.5 Wiring for Proprietary Security Alarm Applications
Table 4.6 shows typical wiring for proprietary security alarm applications with FMM-1 modules.
Note the following:
The module is programmed with software
For use with UL listed systems only; application not for ULC security usage.
NAC devices used for security cannot be shared with fire NAC devices.
Refer to the Device Compatibility Document for compatible NAC devices.
All monitor modules used for security application must be installed in the NFS2-640/E cabinet
with STS-1 Security Tamper Switch.
UL-listed 47K
UL-listed,
End-of-Line Resistor
normally-open
(provided with module)
security switch
UL-listed, normally-closed
security switch
Figure 4.6 Wiring Diagram for Proprietary Security Alarm Applications
54
SECURITY
NFS2-640/E Protected Premises Unit
FlashScan Monitor Module
NFS2-640/E Installation Manual — P/N 52741:P2 7/10/14
Fire/Security Applications
Type Code.
SLC
Channel
A or B
*If the SLC device does
not match the one in this
figure, refer to the SLC
manual appendix, which
contains wiring conversion
charts for type V and type
H modules.