Lynx Plus Series Installation and Setup Guide
System Communication
.
Report
3+1/4+1 Standard
Alarm
SSS(S) A
Trouble
SSS(S) T
Bypass
SSS(S) B
AC Loss
SSS(S) E
Low Battery
SSS(S) L
Open
SSS(S) O
Close
SSS(S) C
Test
SSS(S) G
Restore Alarm
SSS(S) R
AC Restore
SSS(S) R A
Low Battery Restore
SSS(S) R L
Trouble Restore
SSS(S) R T
Bypass Restore
SSS(S) R B
ADEMCO Contact ID® Reporting takes the following format: CCCC Q EEE GG ZZZ where:
CCCC = Customer (subscriber) ID
Q = Event qualifier, where: E = new event, and R = restore
EEE = Event code (3 hex digits) (for a complete list of event codes, refer to the central office receiver manual)
GG = Always "00"
ZZZ = Zone/Contact ID® number reporting the alarm, or user number for open/close reports. System status
messages (AC Loss, Walk Test, etc.) contain zeroes in the ZZZ location.
Code
110
Fire Alarm
121
Duress
122
Alarm, 24-hour Silent
123
Alarm, 24-hour Audible
131
Alarm, Perimeter
132
Alarm, Interior
134
Alarm, Entry/Exit
135
Alarm, Day/Night
146
Silent Burglary
150
Alarm, 24-Hour Auxiliary
162
Alarm, Carbon Monoxide Detector
301
AC Power
302
Low System Battery/Battery Test Fail
344
RF Jam Detected
353
ECP Communication/Supervision failure, case
tamper or low battery
373
Fire Loop Trouble
374
Exit Error Alarm
Notes: (1) The following codes are logged in the event log upon occurrence, but are not reported:
305 = System Reset
627 = Keypad Program Mode Entry
(2) LRR/IP Communications Module Low Battery and Low Battery restore reports are sent real time. LRR/IP Communications
Module trouble restore report is sent after two CODE + OFF (only if physically restored).
3+1/4+1 Expanded
SSS(S) A
AAA(A) Z
SSS(S) T
TTT(T) t
SSS(S) B
BBB(B) b
SSS(S) E
EEE(E) A C
SSS(S) L
LLL(L) L B
SSS(S) O
OOO(O) U
SSS(S) C
CCC(C) U
SSS(S) G
GGG(G)g
SSS(S) R
RRR(R) Z
SSS(S) R A
R A R A R A (R A )A c
SSS(S) R L
R L R L R L (R L )L B
SSS(S) R T
R T R T R T (R T )t
SSS(S) R B
R B R B R B (R B )b
CONTACT ID® EVENT CODES
Definition
4+2
SSSS AZ
SSSS Tt
SSSS Bb
SSSS EA C
SSSS LL B
SSSS OU
SSSS CU
SSSS Gg
SSSS RZ
SSSSR A A c
SSSS R L L B
SSSS R T t
SSSS R B b
Code
380
Global Trouble, Trouble Day/Night
381
RF Supervision Trouble
383
RF Sensor Tamper (Trouble)
384
RF Sensor Low Battery
401
Disarmed, Armed AWAY (NO DELAY), Armed AWAY
403
Scheduled Auto Arm
406
Cancel by User
407
Remote Arm/Disarm (Downloading)
408
Quick Arm AWAY/NO DELAY
441
Disarmed/Armed Stay/No Delay, Quick Arm Stay/No
Delay
459
Recent Close
570
Bypass
602
Periodic Test
606
AAV to follow
607
System Test
623
Event Log 80% Full
654
System Inactivity
- 64 -