Safety Devices - Daikin VRV IV+ Service Manual

Table of Contents

Advertisement

https://daikin-p.ru/catalog/vrv-daikn/naruzhnye-vrv-bloki-daikin
6.6

Safety devices

Wiring
Component
symbol
T1A
Current sensor
S1PH,
High pressure switch
S2PH
S1NPH
High pressure sensor
S1NPL
Low pressure sensor
M1C, M2C Compressor
JT16KBVDYR@S
M1C, M2C Compressor
JT16KBVDYR@S
M1C, M2C Compressor
JT1GUVDYR@BA
M1C, M2C Compressor
JT1GUVDYR@BA
R21T,
Discharge pipe
R22T
thermistor
R8T, R9T Compressor body
thermistor
R8T, R9T Compressor body
thermistor
R21T,
Discharge pipe
R22T
thermistor
R8T, R9T Compressor body
thermistor
A3P, A6P,
Radiation fin
A4P, A7P
temperature
Drop control is visible through service checker tool.
Retries are monitored by field setting Mode 1 (monitor mode):
1-23/24/25. See
"6.9 Field settings" on
Forced stops will trigger error codes. Active errors are visible on the
outdoor unit 7-Segment LED Display, remote controller displays and
central controller devices. To consult the error history, see "To check
the error history" in
"2 Troubleshooting" on
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ Heat Pump
ESIE18-14 – 2019.07
Description
Trigger
Earth leakage protection T1A > 75 mA (± 25%)
High pressure protection High pressure >4.0 MPa (+0.00, -0.15)
Reset: high pressure <3.0 MPa±0.15
High pressure protection High pressure >3.72 MPa
Retry 3 times in 40 minutes
High pressure >3.55 MPa in cooling mode
Reset: High pressure <3.04 MPa
High pressure >3.04 MPa in cooling mode
Reset: High pressure <2.89 MPa
High pressure >4.15 MPa (means high
pressure switch failed to open)
Low pressure protection Low pressure <0.07 MPa
Retry 3 times in 60 minutes
Low pressure <0.35 MPa in cooling mode
Reset: Low pressure >0.4 MPa
Low pressure <0.17 MPa in heating mode
Reset: Low pressure >0.23 MPa
Low pressure <0.07 MPa
th
4
retry in 60 minutes
Current protection
Current >28 A
Current protection
When current >28 A, three times in
60 minutes
Current protection
When current >17 A
Current protection
When current >17.6 A, three times in
60 minutes
Overheat protection
Temperature >135˚C for 2 times within
100 minutes
Reset: Temperature <95˚C
Temperature >108˚C
Reset: Temperature <95˚C
Overheat protection
Temperature >108˚C
Overheat protection
Temperature >135˚C for 3 times within
100 minutes
Reset: Temperature <100˚C
Overheat protection
Temperature >120˚C for 2 times within
10 minutes
Reset: Temperature <100˚C
Overheat protection
Temperature >120˚C for 2 times within
10 minutes
Reset: Temperature <100˚C
Overheat protection
Temperature >110˚C
Reset: Temperature <107˚C
Temperature >114˚C
page 188.
page 9.
6 Technical data
Error
Action type
E2
Drop control
E3
Forced stop
E3
Drop control
Drop control
Drop control
JA
Forced stop
E4
Drop control
Drop control
Drop control
E4
Forced stop
Drop control
L8
Forced stop
Drop control
L8
Forced stop
F3
Forced stop
Drop control
Drop control
F3
Forced stop
F3
Forced stop
F3
Forced stop
Drop control
L4
Forced stop
Service manual
183